Description
Analog Output Module Modicon Quantum – 4 O
| range of product |
Modicon Quantum automation platform
|
|
|---|---|---|
| product or component type |
Analogue output module
|
| analogue output number |
4
|
|
|---|---|---|
| addressing requirement |
4 output words
|
|
| analogue output range |
+/- 10 V >= 1000 Ohm bipolar voltage
+/- 5 V >= 500 Ohm bipolar voltage 0…10 V >= 1000 Ohm unipolar voltage 0…5 V >= 500 Ohm unipolar voltage |
|
| analogue output resolution |
12 bits
|
|
| analogue output current |
-10…10 mA
|
|
| source resistance |
0.1 Ohm
|
|
| cable distance between devices |
400 m
|
|
| absolute accuracy error |
+/- 0.15 % of full scale at 77 °F (25 °C)
|
|
| linearity |
+/- 1 LSB
|
|
| accuracy drift according to temperature |
0.003 % of full scale/°C unipolar
0.004 % of full scale/°C bipolar 0.005 % of full scale/°C maximum unipolar 0.007 % of full scale/°C maximum bipolar |
|
| isolation between channels |
500 V for 1 minute 47…63 Hz AC
|
|
| isolation between channels and bus |
780 V for 1 minute AC
|
|
| update time |
3 ms
|
|
| setting time |
700 µs to +/- 0.1 % of the final value maximum
|
|
| bus current requirement |
700 mA
|
|
| power dissipation in W |
<= 4.5 W
|
|
| associated fuse rating |
0.063 mA 3 AG fast blow 250 V
|
|
| marking |
CE
|
|
| local signalling |
4 LEDs green channel is turned on
4 LEDs red channel fault 1 LED green bus communication is present (Active) 1 LED red external fault |
|
| module format |
Standard
|
|
| product weight |
0.66 lb(US) (0.3 kg)
|
| product certifications |
CUL
FM Class 1 Division 2 |
|
|---|---|---|
| standards |
UL 508
CSA C22.2 No 142 |
|
| resistance to electromagnetic fields |
9.14 V/yd (10 V/m) 80…2000 MHz conforming to IEC 801-3
|
|
| ambient air temperature for operation |
32…140 °F (0…60 °C)
|
|
| ambient air temperature for storage |
-40…185 °F (-40…85 °C)
|
|
| relative humidity |
95 % without condensation
|
|
| operating altitude |
<= 16404.2 ft (5000 m)
|